Soffit Calculator
Soffit is estimated on panel coverage, not panel width: a 12 inch vinyl panel covers 11.5 inches once the lock is engaged. This counts on the real figure, and checks whether your vented panels actually deliver the intake air the attic needs.
The formulas
Panel count
Panels = (Eave run × (1 + Waste)) ÷ Panel coverage width
Coverage width, not nominal width. A 12 in vinyl panel covers 11.5 in once locked, so counting on 12 in leaves you roughly 4% short — about five panels on a 120 ft eave.
Sticks to buy
Sticks = Panels ÷ floor(Stock length ÷ Overhang depth)
Panels are cut from 12 ft stock. An 18 in overhang yields 8 cuts per stick with a little waste; a 24 in overhang yields exactly 6. Awkward overhangs waste material, which is why the offcut per stick is worth checking.
Ventilation required
Intake NFA = (Attic area ÷ 300) × 144 × 50%
The IRC allows 1 sq ft of net free area per 300 sq ft of attic when intake and exhaust are balanced, and expects roughly half of it at the eave. Multiplying by 144 converts square feet to square inches, which is how vent products are rated.
Ventilation provided
Provided NFA = Eave run in feet × NFA per linear foot
Net free area is the actual open area for airflow, far less than the perforated area you can see. A fully vented vinyl panel gives about 9 sq in per linear foot; use your manufacturer figure if you have it.
Worked example
A typical single-storey house
A 120 ft eave run with an 18 in overhang in vinyl, 10% waste. The run with waste is 1,584 in; divided by 11.5 in of coverage that is 138 panels, cut 8 to a 12 ft stick — 18 sticks. Channel comes to 22 sticks for both sides.
138 panels
Panels per 100 feet of eave
Before waste. The difference between nominal and actual coverage is the column that catches people out.
| Material | Nominal width | Actual coverage | Panels per 100 ft |
|---|---|---|---|
| Vinyl soffit | 12 in | 11.5 in | 105 |
| Aluminium soffit | 12 in | 11.5 in | 105 |
| Fibre cement sheet | 48 in | 48 in | 25 |
| Plywood sheet | 48 in | 48 in | 25 |
Attic ventilation required by attic size
Net free area in square inches, using the balanced 1/300 ratio with half the total at the eave. The last column is the eave run of fully vented vinyl soffit that supplies it.
| Attic floor area | Total NFA | Intake NFA at eave | Vented soffit needed |
|---|---|---|---|
| 800 sq ft | 384 sq in | 192 sq in | 22 ft |
| 1,000 sq ft | 480 sq in | 240 sq in | 27 ft |
| 1,500 sq ft | 720 sq in | 360 sq in | 40 ft |
| 2,000 sq ft | 960 sq in | 480 sq in | 54 ft |
| 2,500 sq ft | 1,200 sq in | 600 sq in | 67 ft |
| 3,000 sq ft | 1,440 sq in | 720 sq in | 80 ft |
Values used
Every number this calculator applies on your behalf is listed here, with its source. If your supplier quotes a different figure, use theirs — materials vary by region and grade.
| Value | Used | Typical range | Source |
|---|---|---|---|
| Vinyl panel net coverage | 12 in | 11–12 | Vinyl Siding Institute |
| Net free area, fully vented panel | 9 | 7–12 | Home Ventilating Institute |
| Attic ventilation ratio | 300 | 150–300 | International Code Council |
| Default waste allowance | 10 % | 5–15 | — |
- Vinyl panel net coverage: A 12 in nominal panel covers 11.5 in once the lock is engaged. Estimating on 12 in under-orders by about 4%.
- Net free area, fully vented panel: Square inches per linear foot. Manufacturers publish their own figure — use theirs if you have it.
- Attic ventilation ratio: 1 sq ft of net free area per 300 sq ft of attic floor when vents are balanced between eave and ridge; 1 per 150 otherwise.
- Default waste allowance: Cuts at corners and returns. Raise it for a house with many gables or a wrapped porch.
Common questions
How do I calculate how much soffit I need?
Measure the total eave run around the house and the overhang depth from wall to fascia. Multiply for area, then divide the run by the panel coverage width — 11.5 inches for standard vinyl, not the 12 inches printed on the box. Add 10% for cuts at corners and returns.
Why does a 12 inch soffit panel only cover 11.5 inches?
The lock on one edge and the nail hem on the other overlap the neighbouring panel, so half an inch of each panel is hidden. Over a 120 foot eave that difference is five extra panels — enough to send you back to the supplier if you estimated on nominal width.
How much vented soffit do I need?
The IRC wants 1 square foot of net free ventilating area per 300 square feet of attic floor when intake and exhaust are balanced, with about half of it at the eave. For a 1,500 sq ft attic that is 360 square inches of intake — about 40 feet of fully vented vinyl soffit at 9 sq in per foot.
Do I need vented soffit all the way round?
Not usually. Alternating vented and solid panels halves the intake area and is still enough on many houses. What matters is the total net free area, and that it is balanced against the exhaust at the ridge — intake without exhaust does not ventilate anything.
What is the difference between J-channel and F-channel?
J-channel holds a panel edge and is used against the wall. F-channel has a flat leg that fastens to the fascia board and a slot that receives the panel, so it is used on the outer edge. A typical job needs one run of each along the whole eave.
How wide can a soffit span without support?
About 24 inches for vinyl or aluminium. Beyond that the panels sag in summer heat, so add nailers between the wall and the fascia, or switch to fibre cement or plywood, which are stiff enough to span further.
Keep going
Related calculators
- Roof pitch calculator
Pitch, true roof area and rafter length
Guides
- How much soffit do I need?
Measuring the eave, and the coverage-width trap
- Attic ventilation requirements
Net free area, the 1/300 rule, and what each vent delivers
Costs
- Soffit and fascia cost
Installed prices per linear foot
Sources
- International Residential Code, Section R806: Roof Ventilation — International Code CouncilThe 1/150 and 1/300 net free ventilating area rules, and the balanced-vent condition.
- Vinyl Siding Installation Manual — Vinyl Siding InstitutePanel coverage, channel selection and fastening practice for vinyl soffit.
- Net free area ratings for ventilation products — Home Ventilating InstituteTypical NFA per linear foot for vented soffit panels.
Reviewed by Quban, Construction estimator, on . How these numbers are checked.